Pump Technology Logo

Dry-Deck 20

Installation Instructions

Model Number SDP073R

  Home   

Content List                     To jump to a section click on the description listed

1. Introductory Schematic
2. Introduction & Principles of Operation
3. Installation & User Warnings
4. Pump Installation
5. Plumbing the Waste Pipe
6. Plumbing the Gulley
7. Using the Dry-Deck with a Macerator Pump
8. Connecting the Flow Sensor
9. Control Unit Installation
10. Schematic of Dry-Deck 20 Components
11. Electrical Connections
12. Auxiliary Functions
13. Principles Of Operation
  How to Adjust Settings
14. Setup          Inlet Pipe Size
                     Pump Start Up - Start Delay
                     Pump Flow Rate - Pump Speed Settings
                     Pump Speed - Narrow Setting
                     Pump Shut Down - Over Run (Autosense)
                                                  - Over Run (Fixed)
                     Commissioning Checklist
15 Dry-Deck 20 Set up Flow Chart
16. Pump Operation
17. Warranty
18. EU Declaration Of Conformity
19. Dry-Deck 20 Status Information
20. Dry-Deck 20 Fault Diagnosis Chart
  Components & Dimensions          Control Unit
                                                          Pump - SDS041T
                                                          Surge Damper
                                                          50mm Gulley - 755.140
                                                          90mm Gulley - AK1695
                                                         Vinyl Floor Gulley - AK1610
                                                         Tiled Floor Gulley - AK1615
                                       Available Spare Parts

 

1.  Introductory Schematic

Dry-Deck 20 Installed Diagram

Return to Content List

2. Introduction and Principles Of Operation

Thank you for purchasing this Dry-Deck 20 product from Pump Technology Ltd.

 

Since 1995 Whale have been the leading manufacturer of pump kits for use with shower trays and wet floors.

These kits have the reputation of working reliably for many years without requiring maintenance.

Section 1 above shows the product installation in an apartment with the components in an adjacent airing cupboard.

Look at your installation prior to fitting so that the pump, surge damper, control unit and sensors are in accessible positions.

Typical installations would have these components in an adjacent cupboard i.e. airing cupboard or in a false wall with an access panel.

Warning Please note: incorrect installation may invalidate the warranty.

Principles Of Operation

       This Dry-Deck 20 control unit uses flow sensors to measure the flow rate of water into the shower.

The pump speed is controlled directly by the control unit which uses the signals sent from the flow sensors to adjust the pump speed to match the flow from the shower.

This minimizes suction noise at the gulley. A simple setup is required to match the pump performance to the characteristics of the installation.

Return to Content List

3. Installation & User Warnings

                 Installation Warnings

 

Before Installation read the instructions.
Contact the Technical Helpline (0845 0694 253) if you are unsure.
All electrical and mechanical components (control unit, pump and flow sensors) must be accessible after installation.
The MAXIMUM flow rate the pump is designed to work with is 20 Litres/Minute
Do not plumb the pump outlet into the waste piping that other appliances drain into as there is a risk of induced syphoning. Use an anti-syphon trap where necessary.
The shower floor must have a fall of 30mm in 1metre to the gulley.
Plumbing installations must comply to latest WRAS regulations.
The electrical wiring must conform to EU wiring regulations BS7671:2001 Amdt2:2004.

 

                User Warning

It is advisable where the property is unattended for an extended period that the water supply to the shower is shut off.
If there is a reduction in pump performance after installation please contact your installer.

 

         Wet Floor / Shower Tray Warning

The Dry-Deck 20 system is designed to work on shower bases with an adequate fall to the gulley. We would recommend the use of pre-formed shower bases, i.e. Impey Aqua-Dec or similar. This eliminates the risk of puddling or insufficient fall to the gulley.

Where the floor is being formed in the screed we recommend the following falls:

30mm in 1 metre

15mm in 500cm

7.5mm in 250mm

Forming a shower base is a highly skilled task, do not attempt this if you are unsure.

Where the fall is not sufficient the water will not refill the gulley rapidly enough and so suction noise will be increased dramatically.

Call the Technical Helpline on 0845 0694 253 if you are unsure.

Return to Content List

 

4. Pump Installation

 

1. Before mounting the pump refer to the plumbing diagram in the next section for maximum pipe runs.

Mount the pump on a solid wall to prevent vibration. Use a back board if this is not possible.

The pump is mounted vertically (See opposite) within 3m of the gulley.

To aid servicing the head of the pump must be above the floor by at least 150mm (maximum height of 500mm).

Fix the pump in position through the feet with the screws and washers provided.

Pump Mounting Diagram

2. Rotate the pump head if necessary to give a straight run of pipe to the waste. Loosen the clamping rings on the pump head and rotate the head before retightening clamping rings.

Note: Do not remove the pump head.

Pump Head Diagram

3. Push fit fittings are provided to connect the pump to inlet and discharge pipe work.

All pipe work in and out of the pump must be in 22mm.

Ensure fittings are locked after the pipe has been pushed home.

Push Fittings Diagram

Return to Content List

 

5. Plumbing the Waste Pipe

Pipe Length Diagram

Only one vertical lift on the inlet to the pump and the discharge from the pump is allowed.
When laying the pipe under the floor use only slow radius bends.
Use slow radius bends above the floor if possible to ease the flow of water and reduce loading on the pump.
Use of copper pipe is recommended to reduce the risk of air leaks at connections.
Ensure edges are burr-free. Burrs may cause a build up of hair etc. that will reduce flow.
Pipe work must be secured to prevent any vibration and noise.
Twist lock the securing ring on the push fit fittings (If semi rigid pipe is being used follow the manufacturers instruction to prevent air leaks).

Surge Damper Fitted Diagram

Return to Content List

 

6. Plumbing the Gulley

Use silicone on top of the seal to ensure proper sealing beneath tray. Using the hand tool provided to tighten the locking flange, fit the gulley cover into the sockets and push down with the palm of your hand to secure.

When fitting in solid floors, remove enough concrete for the installation of the waste water pipe and gulley. Where copper pipe runs under the concrete it must be lined to protect and prevent corrosion.

Leave the hand tool in place to prevent building debris, grout etc. falling into the gulley. Only remove the hand tool and fit the gulley cover when the installation is complete.

For alternative gulley options Click Here.

Gulley Installation Diagram

Return to Content List

 

7. Use with a macerator pump

Where the situation demands or if the pipe run is greater than that specified for the Whale pump a macerator pump may be used.

Contact the technical helpline (0845 0694 253) for assistance.

The discharge from the pump must go into the top of the macerator box and not into lower side entries.

DO NOT USE the bottom entries.

It is preferable to have two separate discharge lines to waste and drainage when used in the same room as a macerator pump.

Warning:- Failure of the macerator will not be detected by the Whale Pump.

Macerator Pump Diagram

Return to Content List

 

8. Connecting the Flow Sensor

Fit the Flow Sensors with the arrow in the direction of flow to the shower, downstream of any other connections to the water supply. Each sensor must be protected by a filter which is supplied in the kit.

The flow sensor must be mounted in a straight length of unstressed pipe.

WarningNote: Do not remove, tighten or tamper with this device.

Failure to comply will invalidate your warranty.

 

 

Flow Sensor & Filter Diagram

 

 

Return to Content List

 

9. Control Unit Installation

Locate the control unit outside the showering area (as per BS7671:2001 in zone 2 or 3, refer to the drawing)

The control unit meets IP45.

Tighten all cable entry grommets, even unused ones, to seal the Control Unit.

Connect Control Unit to 240v AC supply via a 5 amp fused spur.

Dry-Deck 20 Control Box Diagram

BS7671:2001 Bathroom Zone Diagram

Return to Content List

 

10. Schematic of Dry-Deck 20 Components

 

Schematic of Dry-Deck 20 Components

Return to Content List

 

11.Electrical Connections

Switch off the power to the control unit while making connections.

Mount the control unit in a position where it is not easily accessible to the user. The enclosure is IP45 rated and may be mounted in zone 2 of the bathroom.

Strip wires 10mm and twist prior to inserting into the spring loaded contacts. Push contact arm back with a finger or small screwdriver before inserting wire and then release.

Check for a good connection by gently tugging on the wire.

1. Connect pump supply wires to the Pump Red and Pump Black connections.

2. Connect flow sensor to sensor connections using the colours as indicated on the controller board.

For the cold supply use FS1 and for the hot supply use FS2 connections - see diagram on the right.

Control Box Electrical Connections

Return to Content List

 

12.Auxilary Functions

1. LED Display: When not in programming mode the display shows ' - - '

Water flowing through the flow sensor is indicated by alternately flashing ' flow rate ' for flow sensor 1 and ' flow rate ' for flow sensor 2. When no water is flowing the display flashes ' - - '. Flow rate is displayed in 0.1 litre increments up to 10 litres and then 1 litre increments.

 

2. Flow Rate Display: When the system is not in status display mode or configuration mode, it will display the flow rate on the 7 segment LED's

With no water flowing the system will display ' - - ' momentarily every few seconds.

With water flowing the system will display the following:

Sensor 1 flow rate, Sensor 2 flow rate, Combined flow rate.... repeating

Flow rates up to 9.9 litres/minute will be displayed to 1 decimal place.

Flow rates of 10 litres/minute and above will display the rate as the nearest whole number.

For Example:

3.4 litres/minute on inlet 1 - LED shows "3.4"

7.5 litres/minute on inlet 2 - LED shows "7.5"

Then total flow is displayed - "11"

 

3. Solenoid Switch: See Diagrams 1.13 and 1.14 below.

Aux 1 is for connection to a momentary contact switch. When the user closes the switch Solenoid 1 and Solenoid 2 are energised for 30 minutes. This allows water to flow through the shower. If the switch is closed again the 30 minute timer starts again.

Technical Specification of Solenoids

Voltage:                  24V a/c

Power Draw:          6VA

Pressure Range:   0.2 - 10 bar

Approvals:              EN60730-2-8, WRAC

 

4. Pump Run Switch: See Diagrams 1.13 and 1.14 below.

Aux 2 is for connection to a momentary contact switch. When pressed the pump runs for 2 minutes and enters the over run cycle. This may be used where the wet room is washed down and water needs to be pumped away.

Return to Content List

 

13. Principles Of Operation - Four Stages of Controller Operation

1. Pump Start: The pump controller measures the volume of water released into the shower tray. The installer sets this volume so that there is water in the gulley before the pump starts thus preventing any start up sucking noise.
2. Pumping flow rate: With the shower running at a mid flow (8 litres/minute) setting the installer adjusts pump speed to match the flow of water into the tray. This is done by watching the level of water at the gulley and adjusting the speed up or down as required until the water is being pumped away slightly faster than the flow from the shower.
3. Pump Speed Narrow setting: The pump speed-narrow setting is used to set the pump speed at 2 litres/minute increments above 8 litres/minute up to the maximum flow from the shower. This is necessary as flow characteristics from the pump change at higher rates.
4. Pump Shutdown: After the pump speed is set the shower is turned off. When the water is drained from the tray a gurgling noise is heard. The electric current loading on the pump is then stored for subsequent use in automatically turning off the pump.
How to adjust settings:  

a. Pressing the Mode button will switch between the various mode settings, indicated by small LED's.

b. The Up and Down arrows are used to adjust the value.

c. Press down the Mode button firmly until the LED flashes which indicates that the selected value has been stored.

Switch power on to the control unit - the LED's will blink alternately. A simple setup is all that is required for trouble-free efficient performance of the Dry-Deck 20 system.

Return to Content List

14. Setup

See flow chart below (click here)

Inlet Pipe Size:

Programme in the size of pipe work from the gulley to the pump. Select 22mm. Ignore the 15mm setting as this is not used for this application. With '22' illuminated on LED's hold the mode button down firmly until the LED blinks.

Note: This will also reset all the factory default settings including the pump speed.

Pump Start Up: Start Delay (litres):

This selects the initial amount of water in the tray before pumping starts. This should come above the level of the gulley. (Factory default is the minimum setting of 0.4 litres). Pressing the Up arrow will increase the amount of water from 0.4 litres to 5 litres passing through the shower head before the pump starts.

Make adjustments to this setting during final commissioning.

Pumping Flow Rate: Pump Speed Settings:

Prior to making adjustments turn the shower on and wait until the pump runs.

Set the shower flow rate to 8 litres/minute.

Watch the level of water within the shower using the gulley cover as a guide. If the water level is lowering then reduce the speed of the pump by pressing the Down arrow. Use initial increments of 5 until fine tuning is required. When the water level is rising then increase the speed of the pump using the Up arrow.

After making a change watch the water level. Wait at least 30 seconds, as the system needs to stabilise, until you see if the water is rising or falling. When the water level is slightly over pumping, program in the speed setting by pressing the Mode button firmly until the LED blinks.

Pump Speed - Narrow setting:

This setting is required for higher flow rates.

a. 'Pump speed' must be set first as per above using a mid-range flow setting.

b. Increase the flow from the shower in increments of 2 litres and watch the water level around the shower gulley. If this is rising or falling over time make adjustments until a constant level is observed then programme in the setting.

c. This process is repeated in 2 litre increments. The narrow adjustment corrects the flow rate over a band of 1 litre/minute either side of the flow rate that is being calibrated.

Pump shut down:- Over Run (Auto Sense) preferred option

To set Auto Sense Over Run (indicated by 'AS' on the LED) you must turn off the shower when you have selected this mode.

When the pump is drawing air there will be a gurgling noise at the gulley, press down the Mode button so the controller stores the loading on the pump at this point.

Pump Shut Down:- Over Run (Fixed)

Alternatively to set a fixed Over Run delay use the Up and Down arrows. Each digit represents a delay of 5 seconds (i.e. 2 = 10 seconds over run).

Hold the Mode button down to program.

 

Commissioning Checklist

a. All push fittings must have the twist lock in the locked position.

b. Check all plumbing for leaks.

c. Check waste water plumbing for leaks while pump is running.

d. Ensure flow sensor is unstressed.

After programming all the settings, turn the shower on and check for correct operation. Make final adjustments to the Start Delay if required.

Note: 15 minutes after showering is finished, the pump will switch on for a brief period in order to remove any water that may have pooled.

Return to Content List

 

15. Dry-Deck 20 Set Up Flow Chart

Dry-Deck 20 Set Up Flow Chart

Return to Content List

 

16. Pump Operation

The Whale Gulper pump uses a single membrane to pump the water away. On the suction stroke, water and debris are drawn in through the inlet valve. With a chamber full of water the pump discharges the water through two non-return valves on the outlet. The two outlet valves protect the pump against losing prime. The aggressive flushing keeps the pump valves clear of debris resulting in a pump which does not require regular maintenance.

Unlike other pumps, the Whale Gulper has the ability to run dry without causing damage to the pump.

An additional advantage of the three non-return valves in the pump head is that no smells can be passed back from the waste stack into the shower area.

 

 

Return to Content List

 

17. Warranty

The Dry-Deck 20 product is guaranteed for two years from date of purchase against defects in materials and workmanship. If the system proves faulty, return it to your distributor with proof of purchase and purchase date. The manufacturer cannot be held responsible for claims arising from incorrect installation, unauthorised modification or misuse of the product. Incorrect installation may invalidate the warranty.

For a full warranty statement please refer to the manufacturers website at www.whalepumps.com

Description of Equipment: Dry-Deck 20 Shower Drain System

Return to Content List

 

18. EU Declaration of Conformity

Description of Equipment: Dry-Deck 20 Shower Drain System

Manufacturer's Declaration

We hereby declare, under our sole responsibility, that the above equipment complies with the provisions of the following EC Directives.

Electromagnetic Compatibility Directive 89/336/EEC, amended by 92/31/EEC and 93/68/EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility.

Low Voltage Directive 73/23/EEC amended by 93/68/EEC on the harmonization of the laws of the Member States relating to electrical equipment designed for use within certain voltage limits.

CE mark affixed: 03/06/05

Basis on which conformity is declared

The above equipment complies with the protection requirements of the EMC Directive and the principle elements of the safety objectives of the Low Voltage Directive.

 

 

 

Standards Applied

EN 60335-1:2002/A11:2004 Safety of household and similar electrical appliances.

EN 60335-2-41:2003 Particular requirements for pumps.

EN 55014-1:2000 Electromagnetic compatibility. Requirements for household appliances, electric tools and similar apparatus. Emission.

EN 55014-2:1997 Electromagnetic compatibility. Requirements for household appliances, electric tools and similar apparatus. Immunity.

Please contact the Whale Technical Helpline 0845 0694 253 for help with any queries

Signed (Authorised Person)

David Cresswell                                          Engineering Director

Munster Simms Engineering Ltd.                            277-279 Old Belfast Road,                                Bangor, Co.Down, BT19 1LTN

 

Return to Content List

 

19. Dry-Deck 20 Status Information

The Dry-Deck 20 stores information on the software version and on the usage of the pump.

This information may be accessed by pressing the Up arrow while not in any Set Up mode.

The fields are displayed on the 7 - segment LED's as follows:

00     - Not currently used

14     - Software version / Software revision

ER    - (field separator) 'Error'

01     - Error code (Object location)

02     - Error code (Object ID)

PP    - (field separator) 'Pump Powered' time

01     - Hours powered 100,000's, 10,000's

02     - Hours powered 1000's, 100's

07     - Hours powered 10's, 1's

22     - Minutes powered 0 - 60

PO    - (field separator) 'Pump On' time

02     - Hours pumping 1000's, 100's

07     - Hours pumping 10's, 1's

22     - Minutes pumping 0 - 60

PC    - (field separator) 'Pump Cycles'

12     - Pump cycles 1000's, 100's

10     - Pump cycles 10's, 1's

- -     - (field separator) returns to normal display

Status display mode will be exited if the keys are inactive for a period greater than 10 minutes (same as configuration mode).

 

 

Status display will be exited if either the mode or decrement key is pressed.

Status display will be exited when all fields have been scrolled through.

Last Error Code

Two bytes representing the last recorded is automatically erased after it has been viewed once.

Duration Powered

This is a record for the length of time the system has had power applied to it. It consists of hours and minutes.

Total Pump Run Time

This is a record for the length of time the pump has been running. It consists of hours and minutes.

Total Pump Cycles

This is the total number of times the pump has been activated (0 - 9999).

Currently this is set to increment every time the pump is turned on following an off state so a purge cycle will also trigger the count. (The software could discriminate if required).

Return to Content List

 

20. Dry-Deck 20 Fault Diagnosis Chart

Dry-Deck Fault Diagnosis Chart

Return to Content List

 

Components & Dimensions

Control Unit - 755.176

Control Unit Dimensions Diagram

 

Pump - SDS041T

Dry-Deck 20 Pump Dimensions Diagram

Surge Damper - 755.228

Surge Damper Dimensions Diagram

50mm Gulley - 755.140

50mm Gulley Dimensions Diagram

90mm Gulley - AK1695

90mm Gulley Dimensions Diagram

Vinyl Floor Gulley - AK1610

Vinyl Floor Gulley Dimensions Diagram

Tiled Floor Gulley - AK1615

Tiled Floor Gulley Dimensions Diagram

 

Dry-Deck Spares

Pump Only                          SDS041T

Flow Sensor                        SDS051T

Diaphragm Service Kit      SDS061T

Pump Head Replacement  SDS071T

 for more information or to order either spares or for gulley variations go to www.whale-spareparts.co.uk

Return to Content List

  

ã Pump Technology Ltd. Registered at Company’s House in the UK No.2728695

Unit 56, Youngs Industrial Estate, Aldermaston, Berks RG7 4PW.

Telephone - 0118 9821555 Fax – 0118 9821666 Email – support@pumptechnology.co.uk